Product description:
General Electric AV-Line switchboard; 2000 amp Power Break II Main Breaker, 480 volt, 3 phase, 4 wire, ground fault, NEMA 1. Reconditioned & guaranteed with a one year warranty.
2 Sections: From Right to Left
Main Breaker Panel:
- PQM II Power Quality Meter
- Transient Voltage Surge Suppressor
- 2000 Amp Main Breaker
- Cat# SSD20B220
- 480 Volt AC
- 3 Pole
- Rating Plug: TR20B
- Shunt Trip
- MicroVersaTrip Plus Trip Unit
- Cat# B220LSIG
- LSIG Functions
- Ground Fault
- 1600 Amp Power Break II Breaker
- Cat# SSD16B216
- 480 Volt AC
- 3 Pole
- Rating Plug: TR16B
- Shunt Trip
- MicroVersaTrip Plus Trip Unit
- Cat# B216LSIG
- LSIG Functions
- Ground Fault
- 800 Amp Power Break II Breaker
- Cat# SSD08B204
- 480 Volt AC
- 3 Pole
- Rating Plug: TR4B
- Shunt Trip
- MicroVersaTrip Plus Trip Unit
- Cat# B204LSIG
- LSIG Functions
- Ground Fault
Distribution Breaker Panel
- (2) 1600 Amp Power Break II Breaker
- Cat# SSD16B216
- 480 Volt AC
- 3 Pole
- Rating Plug: TR16B
- Shunt Trip
- MicroVersaTrip Plus Trip Unit
- Cat# B216LSIG
- LSIG Functions
- Ground Fault
- (2) 800 Amp Power Break II Breaker
- Cat# SSD08B208
- 480 Volt AC
- 3 Pole
- Rating Plug: TR8B
- Shunt Trip
- MicroVersaTrip Plus Trip Unit
- Cat# B204LSIG
- LSIG Functions
- Ground Fault
Dimensions:
- Main Panel
- 53" Width
- 60" Depth
- 96" Height
- Distribution Panel
- 45" Width
- 60" Depth
- 96" Height
M567 LOC: Pillar 144